    MS1 series moulded case circuit breaker is one of products developed and manufactured by adopting international advanced technology. It is supplied with rated insulating voltage 550 and 800V and used for circuit of AC 50/60Hz, rated operating voltage AC 400V (or below), rated operating current up to 1600A for infrequent changing over and starting of the motors.The products conforms to IEC60947-2 standard.
ms1
ms1

 

1. Main Technical Specification(table1).

 

Type

Rated

current (A)

 

Polenum-ber

Ratedinsui-

atingvolt-

age(V)

 

Rated

operat-

ingvolt-age(V)

 

Arcing-over

distance (mm)

 

Ultimate short

circuit breaking

capacity (KA)

 

Servies short

circuit breaking

capacity (KA)

 

Operation

perform-ance

 

Utiliza-tioncat-egory
Load Unload
MS1-63L

(6),10

16,20

25 ,32

40,50

63

3, 4 500V 400V 0 25 18 1500   A
MS1-63M 0 50 35
MS1-100L

(10),16

20,25

32,40

50,63

80,100

800V 0(≤50) 35 22
MS1-100M 0(≤50) 50 35
MS1-100H 0(≤50) 85 50 1000  
MS1-225L

100,125

160,180

200,225

250

≤50 35 22
MS1-225M ≤50 50 35
MS1-225H ≤50 85 50 1000  
MS1-400L

225,250 315,350

400

≤50 50 35
MS1-400M ≤100 65 42
MS1-630L

400,500

630

≤100 50 35
MS1-630M ≤100 65 42
MS1-630H ≤100 100 65
MS1-800M

630,700

800

3 ≤100 75 50
MS1-800H ≤100 100 65
MS1-1250M

1000,1250

≤100 100 65
MS1-1250H ≤100 125 75
MS1-1600M 1600 ≤100 150 80

 

Note: 6A without thermal protection

The N-pole of four-poles breaker is sited at the right side of the product has four types:

Type A: Without current trip-lease on N pole which making all the time, not closing and opening with the other three poles.

Type B: Without current trip-release on N pole which closing and opening with the other poles. Type C: With current trip-release which closing and opening with the other three poles.

Type D: With current trip-release which making all the time not closing and opening with the other three poles.

 

2. Protection Characteristic.

The thermodynamic release of a circuit breaker provides the feature of inverse time-delay, while the magnetic release is the instantaneous operation as shown on table 2(distribution circuit breaker) and table 3 (motor protection circuit breaker).

Table2.

Rated current of release (A) Rated current of release (A) Operating current of
1.05In(cold state) Inoperative time(h) 1.30In(heat state) Operative time(h) magnetic release (A)
10≤In≤63 ≥ 1 < 1 10In±20%
63<In≤100 ≥ 2 < 2
100≤In≤800 ≥ 2 < 2 5In±20% 10In±20%

Table3.

Rated current Thermodynamic release ( ambient temperature ) land +40°C marine +45°C Operating current of
of release (A)

1.0In(cold state)

non-trip time(h)

1.20In(heat state)

trip time (h)

1.50In(heat state) trip

time (h)

7.2In(cold state)

trip time(h)

magnetic release (A)
10 ≤ In ≤ 225 ≥ 2 <2 ≤ 4min 4s < Tp ≤ 10s 12In±20%
225 ≤ In ≤ 630 ≤ 8min 6s < Tp ≤ 20s

 

3. Accessories of Circuit breaker.

3.1 The external accessories of the breaker.

1) Wiring diagram of type CDM electromagnetic operation device(fitting AM1-63,100,225) seethe following drawing (wiring diagram of the external accessories of the breaker in the dotted frame)

ms1ex

Code description: SB1 SB2 stand for push button.(provided by users themselves) Number "1" "2" "3" stand for number of wiring terminals.

Voltage rating: AC50Hz 230V 400V DC 220V.

 

2) Wiring diagram of type CD motor-driven operation device (fitting AM1-400 630 800) seebelows (wiring diagram of the external accessories of the breaker in the dotted frame).

ms1exps

Code description: SB1 SB2 stand for push button. (provided by users themselves) "X" stands for line connection terminals Voltage rating: AC50Hz 230V 400V DC 220V.

 

Rotary handle operation device.

The mechanism is used in moulded case circuit breaker to operate the draw-out panel. Power distribution panel and supply box outside the panel by turning the handle ,and to ensure thedoor of panel would not be openned when the breaker being on. The hand-drive mechanism can be equiped with two types of operation, one is "A" model square handle , the other is "B" model round handle.

ms1op

 

3.2 Release pattern and accessories code.

ms1code
ms1code1
ms1code2

According to user's demands, accessories could lead to direct wire outcoming or line wiring terminals could be added (please mark out in case of making order).

 

Under-voltage release.

Wring diagram of the under-voltage module connected externally (the internal accessories in the dotted frame)Ue: AC50Hz 230V, 400V.

ms1re

When the operation voltage is 35%~70% of the rated voltage, the under-voltage release should make the breaker trip correctly.When the operation voltage is 85%~110% of the rated voltage, the under-voltage release should make the breaker close.In case of the operation voltage less than 35% of the rated voltage, the under-voltage should prevent the breaker from closing.Note: Only the under-voltage release should be energized in advanced, the breaker could berecramped and turned-on, otherwise the breaker will be damaged.

 

Shunt release.

Scheme of wiring(the internal accessories in the dotted frame)"K" is the slow motion switch normal-close contact connect the coil in series in the shunt release.It turns-on or turns-off voluntarily as soon as the breaker on or off.

ms1ps

Voltage rating: AC50Hz 230V or 400V, DC 110V 220VThe shunt release should make the breaker trip reliably when the operation voltage is 70%~110%of the rated control voltage.

 

ms1drawing
Type

Outline Dimensions(mm)

Front panel connection

W W1 L L1 L2 H H1 H2 H3 H4 C D E F G W2 W3
MS1-63L 76 50 135 170 117 74 92   7 4 85 28.5 48 22 14 100 75
MS 1-63M 76 50 135 170 117 82 98.5 28 7 4 85 28.5 48 22 14 100 75
MS1-100L 92 60 150 185 132 68 86 24 7 4 88 35.5 50 22 17.5    
MS1-100M 92 60 150 185 132 86 104 24 7 4 88 35.5 50 22 17.5 122 90
MS1-100H 92 60 150 185 132 86 104 24 7 4 88 35.5 50 22 17.5    
MS1-225L 107 70 165 215 144 86 110 24 5 4 102 31.5 50 22 17    
MS1-225M 107 70 165 215 144 103 127 24 5 4 102 31.5 50 22 17 142 105
MS1-225H 107 70 165 215 144 103 127 24 5 4 102 31.5 50 22 17    
MS1-400L 150 96 257 357 224 105 155 38 8 6 128 64.5 89 65 φ6 198 144
MS1-400M 182 116 270 370 234 110 160 43 8 6 134 70 89 65 φ9    
MS1-630L 182 116 270 370 234 110 160 43 8 6 134 70 89 65 φ9 240 174
MS1-630M 182 116 270 370 234 110 160 43 8 6 134 70 89 65 φ9    
MS1-630H 210 140 280 380 243 106 145 33 30 128              
MS1-800M 210 140 280 380 243 106 145 33 30 128              
MS1-800H 210 140 280 380 243 106 145 33 30 128              
MS1-1250M 210 140 393     200                      
MS1-1250H 210 140 393     200                      
MS1-1600M 210 140 393     200                      

 

Type Outline Dimensions(mm)

Installation

Dimensions

Back panel connection Plug-in connection
L4 H5 H6 φD φD1 L5 L6 H7 H8 H9 H10 J K φd1 M A B φd
MS1-63L 117 44 66 8 8                     25 117 3.5
MS 1-63M 117 44 66 8 8                     25 117 3.5
MS1-100L 129 68 108 26 16 92 168 50 62 74 17.5 56 60 6.5 M8 30 129 4.5
MS1-100M 129 68 108 26 16 92 168 50 62 74 17.5 56 60 6.5 M8 30 129 4.5
MS1-100H 129 68 108 26 16 92 168 50 62 74 17.5 56 60 6.5 M8 30 129 4.5
MS1-225L 126 66 110 20 20 94 183 50 69.5 84.5 17.5 54 70 6.5 M8 35 126 5
MS1-225M 126 66 110 20 20 94 183 50 69.5 84.5 17.5 54 70 6.5 M8 35 126 5
MS1-225H 126 66 110 20 20 94 183 50 69.5 84.5 17.5 54 70 6.5 M8 35 126 5
MS1-400L 194 60 120 33 33 169 279 60 83.5 106.5 21 129 60 8.5 M10 44 194 7
MS1-400M 200 65 125 36 36 169 299 60 92 110 21 123 100 8.5 M12 58 200 7
MS1-630L 200 65 125 36 36 169 299 60 92 110 21 123 100 8.5 M12 58 200 7
MS1-630M 200 65 125 36 36 169 299 60 92 110 21  123 100 8.5 M12 58 200 7
MS1-630H   128                           70 243 7.2
MS1-800M   128                           70 243 7.2
MS1-800H   128                           70 243 7.2
MS1-1250M                                    
MS1-1250H                                    
MS1-1600M                                    

                                          le> AM1-1250H 210 140 393 200 AM1-1600M 210 140 393 200

Type Outline Dimensions(mm)

Installation

Dimensions

Back panel connection Plug-in connection
L4 H5 H6 φD φD1 L5 L6 H7 H8 H9 H10 J K φd1 M A B φd
MS1-63L 117 44 66 8 8                     25 117 3.5
MS 1-63M 117 44 66 8 8                     25 117 3.5
MS1-100L 129 68 108 26 16 92 168 50 62 74 17.5 56 60 6.5 M8 30 129 4.5
MS1-100M 129 68 108 26 16 92 168 50 62 74 17.5 56 60 6.5 M8 30 129 4.5
MS1-100H 129 68 108 26 16 92 168 50 62 74 17.5 56 60 6.5 M8 30 129 4.5
MS1-225L 126 66 110 20 20 94 183 50 69.5 84.5 17.5 54 70 6.5 M8 35 126 5
MS1-225M 126 66 110 20 20 94 183 50 69.5 84.5 17.5 54 70 6.5 M8 35 126 5
MS1-225H 126 66 110 20 20 94 183 50 69.5 84.5 17.5 54 70 6.5 M8 35 126 5
MS1-400L 194 60 120 33 33 169 279 60 83.5 106.5 21 129 60 8.5 M10 44 194 7
MS1-400M 200 65 125 36 36 169 299 60 92 110 21 123 100 8.5 M12 58 58 7
MS1-630M 200 65 125 36 36 169 299 60 92 110 21 123 100 8.5 M1 58 58 7
MS1-630H   128                           70 243 7.2
MS1-800M   128                           70 243 7.2
MS1-800H   128                           70 243 7.2
MS1-1250M                                    
MS1-1250H                                    
MS1-1600M                                    

 

front panel connection
back panel connection pickture
back panel connection
plung in connection

 

We are also one of the leading manufacturers and exporters of a wide range of SMC Pole Mounted Junction Boxes (Street Light Boxes). These are manufactured using high grade material and are provided with a protection cover to avoid shocks. These boxes are highly durable and are offered in standard specifications to our clients.

tu dien

We apply a policy of continuous development of its products and reserves the right to make changes in the specifications and technical characteristics without notice, For further information please contact Morstar.

  Reader Comments

Security Code   
You did not use the site, Click here to remain logged. Timeout: 60 second